LW36B-126 Outdoor AC SF6 circuit breaker is a control and protection device to the 50Hz AC and 110kV power system. It can be used as the connector circuit breaker in the circuit. It gained the new product commendatory certificate in 2001 by the national economic and trade committee.
Technical Specification/Parameter
Main technical specification: Altitude: 1000ï¼ÂÂ2500ï¼ÂÂm Ambient temperature: -40ï½ÂÂ+40°C Rated voltage: 126kV Rated current: 3150A Rated frequency: 50 Hz Rated short circuit breaking current: 40 kA Rated short circuit closing current: 100 kA Rated short time withstand current: 40A Rated withstand current(peak):100 kA Rated short time P.F.withstand voltage: earth/gap 230/275 Rated lighting impulse withstand voltage: earth/gap 550/650 Rated short circuit current continous time: 4s Rated step-lost breaking current: 10A Nearby area fault breaking current: 90% 75% Rated line charging closing current: 31.5 A Rated operating sequence: O-0.3s-CO-180s-CO SF6 air pressure (20°Cmeter pressure):0.6MPa Mechanical lifetime: 6000 Times Control loop voltage: DC110 or 220 V